Technical Help

CABLE GLAND & CLEAT SIZING CHART

Core identification :

  • 2 core - Red, Black
  • 3 core - Red, Yellow, Blue
  • 4 core - Red, Yellow, Blue, Black.
  • 5 core & above - number printed cores

Hawke equivelent size code:

  • OS' = 20SS Or 16/20 M20
  • O' = 20S M20
  • 'A' = 20 M20
  • 'B' = 25 M25
  • 'C' = 32 M32
  • 'C2' = 40 M40
  • 'D' = 50 M50
  • 'E' = 63 m63
No Of Cores 1.5MM 2.5MM 4MM 6MM 10MM 16MM
O/D G C O/D G C O/D G C O/D G C O/D G C O/D G C
2 20S 5 13.6 20S 6 14.7 20S 6 15.9 20 7 18.0 25 8 20.0 25 8
3 12.8 20S 5 14.1 20S 6 15.3 20 7 16.6 20 7 19.5 25 9 21.2 25 9
4 13.5 20S 6 15.0 20S 6 16.4 20 7 18.7 20 8 21.1 25 9 22.9 25 10
16MM 20S
O/D G C 20 7
20.0 25 8 25 9
21.2 25 9 25 11
22.9 25 10 32 13
37 32 12 32 14
No Of
Cores
25MM 35MM 50MM 70MM 95MM 120MM
O/D G C O/D G C O/D G C O/D G C O/D G C O/D G C
2 25 9 25 10 32 12 32 12 40 14 40 16
3 32 10 32 12 32 12 32.2 40 14 37.0 40 16 40.4 50 18
4 28.9 32 12 32.1 32 12 32.0 40 14 37.7 40 14 41.7 50 18 47.1 50 20

KEY:

  • O/D = Nominal overall diameter.
  • G = Gland size to suit.
  • C = Telecleat size to suit.

Please note whilst every care has been taken in the preparation of this table, it is intended only as a guide.

Some differences may occur in the manufactured sizes and cable dimensions can vary.

For further technical information please contact I.C.S. sales/technical dept.

SUSTAINED CURRENT RATING IN AMPS FOR 2, 3 & 4 CORE COPPER
BS5467 XLPE/SWA/PVC / BS6724 XLPE/LSF/SWA/LSF

  MAX MAX  
RESISTANCE RESISTANCE
C.S.A. 2 CORE 0/KM 0/KM 3 & 4 CORE
MM2 DIRECT IN DUCTS IN AIR CONDUCTOR ARMOUR DIRECT IN DUCTS IN AIR
1.5 38 31 31 12.1 10.2 32 26 26
2.5 49 41 41 7.41 8.8 42 34 35
4 65 53 55 4.61 7.0 55 45 47
6 81 67 70 3.08 4.06 69 56 59
10 109 89 95 1.83 3.7 92 75 82
16 141 115 126 1.15 3.1 119 96 107
25 183 148 164 0.727 2.4 152 124 140
35 219 178 202 0.524 2.1 182 149 172
50 259 211 244 0.387 1.9 217 177 209
70 317 260 306 0.268 1.3 266 218 263
95 381 313 378 0.193 1.2 319 263 324
120 433 357 437 0.153 1.1 363 300 376
150 485 401 499 0.124 0.74 406 338 430
185 547 455 576 0.0991 0.66 458 382 495
240 632 527 680 0.0754 0.60 529 442 584
300 708 592 775 0.0601 0.54 592 496 666
400 799 669 892 0.0470 0.49 667 570 766

NOTE : FOR FURTHER TECHNICAL INFORMATION PLEASE CONTACT I.C.S.

SWA SPECIFICATIONS

Multi-core XLPE/SWA/PVC To BS5467

Stranded Class 2 copper conductors to BS6360, XLPE insulation Type GP8 to BS7655, Inner PVC sheath

Type 9 to BS7655, Mild galvanised steel wires to BSEN10257-1, Black PVC outer sheath Type 9 to BS7655,

Flame retardant to BS4066 Part 1, 90oC max conductor operating temperature.

Multi-core XLPE/LSF/SWA/LSF To BS6724

Stranded Class 2 copper conductors to BS6360, XLPE insulation Type GP8 to BS7655, Inner LSF sheath

Type LTS1 to BS7655, Mild galvanised steel wires to BSEN10257-1, Black LSF outer sheath Type LTS1 to BS7655. Flame retardant to BS4066/IEC60332 Part 3 Category A (NMV7), 90oC max conductor operating temperature.